ABB RXPSU14n High Speed Tripping Relay

RXPSU14n

Technical Parameters

Linux system

Unique Smartlink technology

SSL data encryption

Support 4G full network pass

Categories: ,
Get a quote, please contact me immediately:
Simon Zhang
dcsplcsales@gmail.com
Phone/Whatsapp/Skype/Wechat: +86 133 6590 9307

Description

Abb ring main unit – safering 36 RMU ABB MV Products


ABB RXPSU14n High Speed Tripping Relay

ABB High Speed Tripping Relay – ABB RXPSU14n Tripping Relay , High Speed Trip Relay without Operation Indicator

ABB RXPSU14n Tripping Relay Technical Specification

  • Type: Electro Mechanical Relay.
  • Protection Type: High Speed Tripping Relay.
Technical Specifications  Details
Model No : RXPSU14n
Relay type RXPSU14n High Speed Tripping
Auxiliary voltage 110/220 V DC
Type of mounting Plug-in base mounting
Contact configurations 6NO+0NC 5NO+1NC 4NO+2NC 3NO+3NC
Typical applications High burden tripping

 

Design and principle
The bistable relays in the COMBIFLEX system, type RXPSU6n and RXPSU14n are composed of the same constructional elements as the established contactors type P8n. Two magnet systems are interconnected by a pivoted element. In the type RXPSU6n with 6 free contacts, only one system has contacts; in type RXPSU14n with 14 free
contacts, both systems have contacts. In each case two contacts are required for changing over the connection of the coils.

The contacts are arranged symmetrically on both sides of the relay coil and armature assembly in two stacks. They are easily accessible and the conversion from N/C to N/O contacts and vice versa is simple. The maximum rated voltage is 250V DC or AC and the material used is hard silver. The following definitions apply for reset and operate
condition. Reset condition – Armature assembly position is away from the base i.e. the upper system has been pulsed and lower system is ready to be pulsed. The flag strips are invisible i.e. white during this condition. Operate condition – Armature assembly position is closer to the base i.e. the lower system has been pulsed and upper system is ready to be pulsed. The flag strips are visible i.e. red during this condition.A transparent, incombustible cover with a gasket
protects the contacts against dirt.

The terminals of the contact stacks themselves to permit two wires of 1.5mm diameter maximum to be secured.
Changeover relays must always be mounted with the contact post horizontal, that is with the base on a vertical surface. The plug-in relay module occupies two seats (2U 12C).